10.4.10.4 Configuration setting
If there is no bypass busbar and therefore no 789 disconnector, then the interlocking for
789 is not used. The states for 789, 7189G, BB7_D, BC_17, BC_27 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1
are designated 0=FALSE and 1=TRUE:
789_OP = 1
789_CL = 0
7189G_OP = 1
7189G_CL = 0
BB7_D_OP = 1
BC_17_OP = 1
BC_17_CL = 0
BC_27_OP = 1
BC_27_CL = 0
EXDU_BPB = 1
VP_BB7_D = 1
VP_BC_17 = 1
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the interlocking
for 289 is not used. The state for 289, 2189G, BC_12, BC_27 are set to open by setting the
appropriate module inputs as follows. In the functional block diagram, 0 and 1 are
designated 0=FALSE and 1=TRUE:
289_OP = 1
289_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
BC_27_OP = 1
BC_27_CL = 0
VP_BC_12 = 1