EasyManua.ls Logo

ABB REC650 - Signals from Bus-Coupler

ABB REC650
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.4.7.4 Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus-sections, the signals BC_12
from the busbar coupler of the other busbar section must be transmitted to the own busbar
coupler if both disconnectors are closed.
en04000484_ansi.vsd
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BCABC_BC
(WA1)A1
(WA2)B1
(WA7)C C
B2
A2
ANSI04000484 V1 EN
Figure 116: Busbars divided by bus-section disconnectors (circuit breakers)
The interlocking functionality in 650 series can not handle the transfer bus
(WA7)C.
To derive the signals:
Signal
BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal
BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
VPBC12TR The switch status of BC_12 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module
(A1A2_DC) is used for different busbars, that is, for both bus-section disconnector
A1A2_DC and B1B2_DC.
1MRK 511 286-UUS A Section 10
Control
249
Application manual

Table of Contents

Other manuals for ABB REC650

Related product manuals