5.1.4 Local HMI functionality
5.1.4.1 Protection and alarm indication
Protection indicators
The protection indicator LEDs are Normal, Pickup and Trip.
Table 4: Normal LED (green)
LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred.
Table 5: PickUp LED (yellow)
LED state Description
Off Normal operation.
On A protection function has picked up and an indication message is displayed.
If several protection functions Pickup within a short time, the last Pickup is
indicated on the display.
Flashing
A flashing yellow LED has a higher priority than a steady yellow LED.
The IED is in test mode and protection functions are blocked.
The indication disappears when the IED is no longer in test mode and
blocking is removed.
Table 6: Trip LED (red)
LED state
Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.
The trip indication is latching and must be reset via communication or by
pressing
.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to one
of the three LED colors when configuring the IED.
Section 5 1MRK 511 286-UUS A
Local human-machine interface
82
Application manual