Signal
189OPTR 189 is open.
289OPTR 289 is open (AB_TRAFO, ABC_LINE)
22089OTR 289 and 2089 are open (ABC_BC)
789OPTR 789 is open.
VP189TR The switch status of 189 is valid.
VP289TR The switch status of 289 is valid.
V22089TR The switch status of 289and 2089 is valid.
VP789TR The switch status of 789 is valid.
EXDU_BB No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module
(A1A2_DC) is used for different busbars, that is, for both bus-section disconnectors
A1A2_DC and B1B2_DC.
Signal
DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DC are
set to 1 (TRUE).
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section
coupler bay (A1A2_BS) rather than the bus-section disconnector bay (A1A2_DC) must
be used. For B1B2_BS, corresponding signals from busbar B are used. The same type of
module (A1A2_BS) is used for different busbars, that is, for both bus-section circuit
breakers A1A2_BS and B1B2_BS.
Signal
189OPTR 189 is open.
289OPTR 289 is open.
VP189TR The switch status of 189 is valid.
VP289TR The switch status of 289 is valid.
EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains the
above information.
For a busbar grounding switch, these conditions from the A1 busbar section are valid: