REC650-A07A – Bus Coupler single breaker 10AI (4I+6U)
S CSWI
Control
S XCBR
Control
S CSWI
Control
S CSWI
Control
S CSWI
Control
SMP PTRC
94 1->0
S CSWI
Control
S CSWI
Control
S CSWI
Control
SES RSYN
25 SYNC
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
Other configured functions
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
EF4 PTOC
51N
IN>
Q CBAY
Control
S SCBR
Cond
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
SEL GGIO
Control
DRP RDRE
Mont.
52
189
289
289G
189G
WA1
WA2
1189G 2189G
CC RBRF
50BF 3I> BF
PH PIOC
50 3I>>
CC RPLD
52PD PD
C MMXU
Meter.
C MSQI
Meter.
V MMXU
Meter.
V MMXU
Meter.
IEC61850
ANSI IEC
Function Enabled
in Settings
132 kV Bus
1000/5
132kV/
110V
132kV/
110V
OC4 PTOC
51/67 3I>
ANSI11000139_2_en.vsd
S SIMG
63
IEC61850
ANSI IEC
Function Disabled
in Settings
ANSI11000139 V2 EN
Figure 4: A typical protection and control application for a bus coupler in single
breaker arrangement