EasyManua.ls Logo

ABB REC650 - Page 62

ABB REC650
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
system. The neutral point resistor gives a 10 A ground-fault current during a zero
resistance ground-fault. This means that the resistance is
22000 3
1270
10
N
/
R
W
= =
GUID-4ECDF824-B17E-436D-A668-ACA06BB375F7 V2 EN (Equation 18)
The total zero sequence impedance of the 22 kV system is:
Z
0
= 3R
N
// j3X
N
// — jX
C
Ω / phase
As the Petersen coil is tuned the zero sequence impedance is:
Z
0
= 3R
N
Ω / phase
The residual voltage during a resistive ground-fault in the 22 kV system is:
0
0 0
1
3 3
1 1
Phase
o
f f
phase
V V
V or
R R
V
Z Z
= =
× ×
+ +
GUID-AD49C138-F37B-4690-9E37-BA2BAD678A17-ANSI V1 EN (Equation 19)
In our case the requirement is that ground-faults with a resistance up to 5 000 Ω shall be
detected. This gives:
0
1
0 20
3 5000
1
3 1270
phase
V
.
V
= =
×
+
×
GUID-42D376ED-052F-4E9B-B4D9-8D679127BC0C-ANSI V1 EN (Equation 20)
Step 1 and step 2 is given the same voltage setting but step 2 shall have longer time delay.
The residual ground-fault protection shall have a definite time delay. The time setting is
set longer than the time delay of the ground-fault protection of the outgoing feeders having
maximum 2 s delay. The time delay for step 1 is set to 3 s and the time delay for step 2 is
set to 4 s.
1. Set GlobalBaseSel to 2
The (LV) winding data should be related to Global base 2.
2. Set Characterist1 to Definite time
3. Set Pickup1 to 20 % of VBase
4. Set t1 to 3.0 s
5. Set Pickup2 to 20 % of VBase
6. Set t2 to 4.0 s
Section 3 1MRK 511 286-UUS A
REC650 setting examples
56
Application manual

Table of Contents

Other manuals for ABB REC650

Related product manuals