Name Type Default Description
IN6 BOOLEAN 0=False Input 6
IN7 BOOLEAN 0=False Input 7
IN8 BOOLEAN 0=False Input 8
Table 134: TONGAPC Output signals
Name Type Description
Q1 BOOLEAN Output 1
Q2 BOOLEAN Output 2
Q3 BOOLEAN Output 3
Q4 BOOLEAN Output 4
Q5 BOOLEAN Output 5
Q6 BOOLEAN Output 6
Q7 BOOLEAN Output 7
Q8 BOOLEAN Output 8
3.14.5.4 Settings
Table 135: TONGAPC Non group settings
Parameter
Values (Range) Unit Step Default Description
On delay time 1 0...3600000 ms 10 0 On delay time
On delay time 2 0...3600000 ms 10 0 On delay time
On delay time 3 0...3600000 ms 10 0 On delay time
On delay time 4 0...3600000 ms 10 0 On delay time
On delay time 5 0...3600000 ms 10 0 On delay time
On delay time 6 0...3600000 ms 10 0 On delay time
On delay time 7 0...3600000 ms 10 0 On delay time
On delay time 8 0...3600000 ms 10 0 On delay time
3.14.5.5 Technical data
Table 136: TONGAPC Technical data
Characteristic
Value
Operate time accuracy ±1.0% of the set value or ±20 ms