A070879 V2 EN
Figure 359: Status indication-based interlocking via the GOOSE messaging
9.1.6 Signals
Table 588: CBXCBR Input signals
Name
Type Default Description
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
AU_OPEN BOOLEAN 0=False
Input signal used to open the breaker
1)
AU_CLOSE BOOLEAN 0=False
Input signal used to close the breaker
1)
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for closed position of apparatus from I/O
1)
1) Not available for monitoring
Table 589: DCXSWI Input signals
Name
Type Default Description
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
Table continues on next page