Name Type Values (Range) Unit Description
FAIL_FLLW Enum 0=No failed
followers
1=Follower 1
2=Follower 2
3=Followers 1+2
4=Follower 3
5=Followers 1+3
6=Followers 2+3
7=Followers
1+2+3
Failed followers
PAR_UNIT_MCC Enum 0=No parall units
1=Trafo 1
2=Trafo 2
3=Trafos 1 and 2
4=Trafo 3
5=Trafos 1 and 3
6=Trafos 2 and 3
7=Trafos 1+2+3
Parallel units included in
MCC calculation
OPR_CNT INT32 0...2147483647 Total number of raise
and lower commands
given in the manual and
automatic modes
OLATCC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.5.19 Technical data
Table 641: OLATCC Technical data
Characteristic
Value
Operation accuracy
1)
Depending on the frequency of the current
measured: f
n
±2 Hz
Differential voltage U
d
= ± 0.5% of the measured
value or ± 0.005 x U
n
(in measured voltages <
2.0 x U
n
)
Operation value = ± 1.5% of the U
d
for Us = 1.0
x U
n
Operate time accuracy in definite time mode
2)
+ 4.0% / - 0% of the set value
Operate time accuracy in inverse time mode
2)
+ 8.5% / - 0% of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time (IDMT) 1 s.
Reset ratio for control operation
Reset ratio for analogue based blockings (except
run back raise voltage blocking)
Typical 0.80 (1.20)
Typical 0.96 (1.04)
1) Default setting values used
2) Voltage before deviation = set Band center voltage.
Section 9 1YHT530004D05 D
Control functions
762 615 series
Technical Manual