4.4.1.8  Monitored data
Table 362: NSPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
NSPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
  Status
4.4.1.9  Technical data
Table 363: NSPTOC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: f
n
 ±2 Hz
±1.5% of the set value or ±0.002 x I
n
Start time 
1)2)
  Minimum Typical Maximum
I
Fault
 = 2 x set 
Start
value
I
Fault
 = 10 x set 
Start
value
22 ms
14 ms
24 ms
16 ms
25 ms
17 ms
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 
3)
Suppression of harmonics DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1) Negative sequence current before fault = 0.0, f
n
 = 50 Hz, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
3) Maximum 
Start value
 = 2.5 x I
n
, 
Start value
 multiples in range of 1.5 to 20
4.4.1.10  Technical revision history
Table 364: NSPTOC Technical revision history
Technical revision
Change
B Minimum and default values changed to 40 ms
for the 
Operate delay time
 setting
C Step value changed from 0.05 to 0.01 for the
Time multiplier
 setting
1YHT530004D05 D Section 4
Protection functions
615 series 451
Technical Manual