7.1.8 Monitored data
Table 528: SSCBR Monitored data
Name Type Values (Range) Unit Description
T_TRV_OP FLOAT32 0...60000 ms Travel time of the CB
during opening operation
T_TRV_CL FLOAT32 0...60000 ms Travel time of the CB
during closing operation
T_SPR_CHR FLOAT32 0.00...99.99 s The charging time of the
CB spring
NO_OPR INT32 0...99999 Number of CB operation
cycle
INA_DAYS INT32 0...9999 The number of days CB
has been inactive
CB_LIFE_A INT32 -9999...9999 CB Remaining life phase
A
CB_LIFE_B INT32 -9999...9999 CB Remaining life phase
B
CB_LIFE_C INT32 -9999...9999 CB Remaining life phase
C
IPOW_A FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase A
IPOW_B FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase B
IPOW_C FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase C
SSCBR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
7.1.9 Technical data
Table 529: SSCBR Technical data
Characteristic
Value
Current measuring accuracy ±1.5% or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0%
(at currents in the range of 10…40 x I
n
)
Operate time accuracy ±1.0% of the set value or ±20 ms
Travelling time measurement +10 ms / -0 ms
Section 7 1YHT530004D05 D
Condition monitoring functions
622 615 series
Technical Manual