The frequent operation counter limit is reached and new sequence is initiated.
The lockout is released when the recovery timer elapses
The protection trip signal has been active longer than the time set with the Max
wait time parameter since the shot initiation
The circuit breaker is closed manually during an auto-reclose sequence and the
manual close mode is FALSE.
9.4.4.6 Protection coordination controller
The PROT_CRD output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses,
tripping and initiation of shot 1 should be fast (instantaneous or short-time
delayed). The tripping and initiation of shots 2, 3 and definite tripping time should
be delayed.
In this example, two overcurrent elements PHLPTOC and PHIPTOC are used.
PHIPTOC is given an instantaneous characteristic and PHLPTOC is given a time
delay.
The PROT_CRD output is activated, if the SHOT_PTR value is the same or higher
than the value defined with the Protection crd limit setting and all initialization
signals have been reset. The PROT_CRD output is reset under the following
conditions:
If the cut-out time elapses
If the reclaim time elapses and the AR function is ready for a new sequence
If the AR function is in lockout or disabled, that is, if the value of the
Protection crd mode setting is "AR inoperative" or "AR inop, CB man".
The PROT_CRD output can also be controlled with the Protection crd mode
setting. The setting has the following modes:
"no condition": the PROT_CRD output is controlled only with the Protection
crd limit setting
"AR inoperative": the PROT_CRD output is active, if the AR function is
disabled or in the lockout state, or if the INHIBIT_RECL input is active
"CB close manual": the PROT_CRD output is active for the reclaim time if the
circuit breaker has been manually closed, that is, the AR function has not
issued a close command
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual"
are effective
"always": the PROT_CRD output is constantly active
Section 9 1YHT530004D05 D
Control functions
706 615 series
Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615 F and is the answer not in the manual?

ABB REF615 F Specifications

General IconGeneral
TypeFeeder Protection Relay
Nominal Frequency50/60 Hz
Rated Current1 A / 5 A
Protection FunctionsOvercurrent, Earth Fault, Under/Over Voltage
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
MountingFlush mounting
Ingress ProtectionIP54 (front), IP20
Operating Temperature Range-25 to +55 °C