Operaon mode
Sengs:
•Circle conductance
•Circle susceptance
•Circle radius
Sengs:
•Susceptance reverse
•Susceptance lt Ang
Sengs:
•Conductance reverse
•Conductance lt Ang
Im(Y
o)
Re(Y
o)
Re(Yo)
Im(Yo)Im(Y
o)
Re(Y
o)
Not applicable in
high resistance earthed
or compensated
systems!
Not applicable in
unearthed systems!
Operaon mode
Yo,Go Yo,Bo Go,Bo Yo,Go,Bo
Sengs:
•Circle conductance
•Circle susceptance
•Circle radius
•Conductance reverse
•Conductance lt Ang
Sengs:
•Circle conductance
•Circle susceptance
•Circle radius
•Susceptance reverse
•Susceptance lt Ang
Sengs:
•Conductance reverse
•Conductance lt Ang
•Susceptance reverse
•Susceptance lt Ang
Sengs:
•Circle conductance
•Circle susceptance
•Circle radius
•Conductance reverse
•Conductance lt Ang
•Susceptance reverse
•Sus
ceptance lt Ang
Im(Y
o)
Im(Y
o)
Re(Yo)
Im(Yo)
Re(Yo)
Im(Yo)
Re(Y
o)
Re(Yo)
GUID-C847609F-E261-4265-A1D9-3C449F8672A1 V1 EN
Figure 161: Admittance characteristic with different operation modes when
Directional mode = "Reverse"
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set with the
Operate delay time setting, the OPERATE output is activated. If the fault
1YHT530004D05 D Section 4
Protection functions
615 series 323
Technical Manual