Parameter Values (Range) Unit Step Default Description
Class1OvInd 1 0=No indication
1=Both edges
2=Rising edge
2=Rising edge Overflow Indication for instance 1
Class1OvFType 1 0...255 10 Function Type for Class 1 overflow
indication for instance 1
Class1OvInfNo 1 0...255 255 Information Number for Class 1 overflow
indication for instance 1
Class1OvBackOff 1 0...500 500 Backoff Range for Class1 buffer for
instance 1
GI Optimize 1 0=Standard
behaviour
1=Skip
spontaneous
2=Only overflown
3=Combined
0=Standard
behaviour
Optimize GI traffic for instance 1
DR Notification 1 0=Disabled
1=Enabled
0=Disabled Disturbance Recorder spontaneous
indications enabled/disabled
Serial port 2 0=Not in use
1=COM 1
2=COM 2
0=Not in use COM port for instance 2
Address 2 1...255 1 Unit address for instance 2
Start delay 2 0...20 char 4 Start frame delay in chars for instance 2
End delay 2 0...20 char 4 End frame delay in chars for instance 2
DevFunType 2 0...255 9 Device Function Type for instance 2
UsrFType 2 0...255 10 Function type for User Class 2 Frame for
instance 2
UsrInfNo 2 0...255 230 Information Number for User Class2
Frame for instance 2
Class1Priority 2 0=Ev High
1=Ev/DR Equal
2=DR High
0=Ev High Class 1 data sending priority relationship
between Events and Disturbance
Recorder data.
Frame1InUse 2 -1=Not in use
0=User frame
1=Standard frame
1
2=Standard frame
2
3=Standard frame
3
4=Standard frame
4
5=Standard frame
5
6=Private frame 6
7=Private frame 7
6=Private frame 6 Active Class2 Frame 1 for instance 2
Table continues on next page
Section 3 1YHT530004D05 D
Basic functions
50 615 series
Technical Manual