en06000607_ansi.vsd
~
21
XS
X
L1
IF
v
V
M
Source
Fault voltage
Pre -fault voltage
X
C
Source voltage
V
M
With bypassed
capacitor
With inserted
capacitor
F
X
ANSI06000607 V1 EN-US
Figure 112: Current inversion on series compensated line
The relative phase position of fault current I
F
compared to the source voltage V
S
depends in general on the character of the resultant reactance between the source and
the fault position. Two possibilities appear:
1
1
0
0
- + >
- + <
S C L
S C L
X X X
X X X
EQUATION1935 V1 EN-US (Equation 105)
The first case corresponds also to conditions on non compensated lines and in cases,
when the capacitor is bypassed either by spark gap or by the bypass switch, as shown
in phasor diagram in figure 113. The resultant reactance is in this case of inductive
nature and the fault currents lags source voltage by 90 electrical degrees.
The resultant reactance is of capacitive nature in the second case. Fault current will for
this reason lead the source voltage by 90 electrical degrees, which means that reactive
current will flow from series compensated line to the system. The system conditions
are in such case presented by equation 106
1
> +
C S L
X X X
EQUATION1936 V1 EN-US (Equation 106)
Section 8 1MRK 502 071-UUS A
Impedance protection
250 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual