Measurement function application for a 380kV OHL
SEMOD54481-12 v11
Single line diagram for this application is given in figure 309:
380kV Busbar
380kV OHL
P Q
800/5 A
ANSI09000039-1-en.vsd
380kV 120V
/
3 3
kV
IED
ANSI09000039 V1 EN-US
Figure 309: Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated
in figure
309 it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRef
using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
general settings as shown in table
65.
level supervision of active power as shown in table 66.
calibration parameters as shown in table 67.
Section 17 1MRK 502 071-UUS A
Monitoring
684 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062