lockout and latching function, event generation and the trip signal duration setting. If
the lockout operation mode is selected, binary input X120:BI4 has been assigned to
RST_LKOUT input of both the trip logic to enable external reset with a push button.
Three other trip logics TRPPTRC3...4 are also available if the IED is ordered with
high speed binary outputs options.
TRPPTRC1
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC1_TRIP
PHIPTOC1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
NSPTOC2_OPERATE
INTRPTEF1_OPERATE
PDNSPTOC1_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
DEFHPDEF1_OPERATE
DEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
EFHPTOC1_OPERATE
EFPADM1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
WPWDE1_OPERATE
WPWDE2_OPERATE
WPWDE3_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
X120_BI4_RST_LOCKOUT
GUID-9C6E7492-616C-460F-9AAD-B75FFC0F0737 V1 EN
Figure 186: Trip logic TRPPTRC1
Section 3 1MRS756378 S
REF615 standard configurations
152 REF615
Application Manual