NOT
IN OUT
X110_BI4_CB_SPRING_CHARGED CB_SPRING_DISCHARGED
GUID-2E6D31BF-26F4-47CF-8E05-295BB466E4AD V1 EN
Figure 355: Logic for start of circuit-breaker spring charging
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. Both functions are
blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker open
signal.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR1
BLOCK ALARM
TCSSCBR2
BLOCK ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-F5BCA344-DDE2-4504-91E7-B5A0EB19A8A3 V1 EN
Figure 356: Trip circuit supervision function
Section 3 1MRS756378 S
REF615 standard configurations
246 REF615