ARCSARC1
BLOCK
REM_FLT_ARC
OPR_MODE
OPERATE
ARC_FLT_DET
ARCSARC2
BLOCK
REM_FLT_ARC
OPR_MODE
OPERATE
ARC_FLT_DET
ARCSARC3
BLOCK
REM_FLT_ARC
OPR_MODE
OPERATE
ARC_FLT_DET
OR6
B1
B2
B3
B4
B5
B6
O
ARCSARC1_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
ARCSARC3_OPERATE
ARCSARC1_ARC_FLT_DET
ARCSARC2_ARC_FLT_DET
ARCSARC3_ARC_FLT_DET
ARCSARC_OPERATE
GUID-2B82370A-5D2B-4CAE-A858-6F04CC83058B V1 EN
TRPPTRC3
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC4
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC5
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC3_TRIP
TRPPTRC4_TRIP
TRPPTRC5_TRIP
X120_BI4_RST_LOCKOUT
X120_BI4_RST_LOCKOUT
X120_BI4_RST_LOCKOUT
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
GUID-0F1C0838-790F-4526-801E-DBA88E061C80 V1 EN
Figure 571: Arc protection with dedicated HSO
The optional autoreclosing function is configured to be initiated by operate signals
from a number of protection stages through the INIT_1...5 inputs. The INIT_6
input in the autoreclosing function block is controlled by a binary input X110: BI2
enabling the use of the external autoreclosing start command. It is possible to create
individual autoreclose sequences for each input.
The autoreclosing function can be inhibited with the INHIBIT_RECL input. By
default, few selected protection function operations are connected to this input. A
1MRS756378 S Section 3
REF615 standard configurations
REF615 363
Application Manual