Table 95: Output contacts X130:10-18
Terminal Description
X130:10 SO1, common
X130:11 SO1, NO
X130:12 SO1, NC
X130:13 SO2, common
X130:14 SO2, NO
X130:15 SO2, NC
X130:16 SO3, common
X130:17 SO3, NO
X130:18 SO3, NC
5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of the
protection relay. Under normal operating conditions, the protection relay is energized
and the contact is closed (X100:3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100:3-4).
Table 96: IRF contact
Terminal
Description
X100:3 IRF, common
X100:4 Closed; IRF, or U
aux
disconnected
X100:5 Closed; no IRF, and U
aux
connected
1MRS756378 S Section 5
IED physical connections
REF615 391
Application Manual