The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY input in DARREC1. The signal, and other required signals, are connected
to the CB spring charged binary inputs in this configuration. The open command from
the autorecloser is connected directly to the binary output X100:PO3, whereas the
close command is connected directly to the binary output X100:PO1.
DARREC1
INIT_1
INIT_2
INIT_3
INIT_4
INIT_5
INIT_6
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
OPEN_CB
CLOSE_CB
CMD_WAIT
INPRO
LOCKED
PROT_CRD
UNSUC_RECL
AR_ON
READY
ACTIVE
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR
B1
B2
O
X120_BI3_CB_OPENED
DARREC1_CLOSE_CB
DARREC1_OPEN_CB
X110_BI3_GAS_PRESSURE_ALARM
X110_BI4_CB_SPRING_CHARGED
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
NSPTOC2_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
INTRPTEF1_OPERATE
PDNSPTOC1_OPERATE
DEFHPDEF1_OPERATE
DEFLPDEF2_OPERATE
WPWDE2_OPERATE
WPWDE3_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
CBXCBR1_SELECTED
DARREC1_INPRO
DARREC1_UNSUC_RECL
GUID-14FC7626-21FE-4F3C-8DCA-36561847D355 V1 EN
Figure 66: Autoreclosing function
The residual overvoltage protection ROVPTOV provides earth-fault protection by
detecting an abnormal level of residual voltage. This can be used, for example, as a
nonselective backup protection for the selective directional earth-fault functionality.
Section 3 1MRS756378 S
REF615 standard configurations
84 REF615
Application Manual