Table 27: Settings parameters for level supervision
Setting Short Description Selected
value
Comments
PMin
Minimum value -100 Minimum expected load
PMax
Minimum value 100 Maximum expected load
PZeroDb
Zero point clamping in 0.001% of
range
3000 Set zero point clamping to 45 MW
that is, 3% of 200 MW
PRepTyp
Reporting type db Select amplitude deadband
supervision
PDbRepInt
Cycl: Report interval (s), Db: In %
of range, Int Db: In %s
2 Set ±Δdb=30 MW that is, 2%
(larger changes than 30 MW will
be reported)
PHiHiLim
High High limit (physical value) 60 High alarm limit that is, extreme
overload alarm
PHiLim
High limit (physical value) 50 High warning limit that is, overload
warning
PLowLim
Low limit (physical value) -50 Low warning limit. Not active
PLowLowlLim
Low Low limit (physical value) -60 Low alarm limit. Not active
PLimHyst
Hysteresis value in % of range
(common for all limits)
2 Set ±Δ Hysteresis MW that is, 2%
Table 28: Settings for calibration parameters
Setting
Short Description Selected
value
Comments
IAmpComp5
Amplitude factor to calibrate
current at 5% of Ir
0.00
IAmpComp30
Amplitude factor to calibrate
current at 30% of Ir
0.00
IAmpComp100
Amplitude factor to calibrate
current at 100% of Ir
0.00
UAmpComp5
Amplitude factor to calibrate
voltage at 5% of Ur
0.00
UAmpComp30
Amplitude factor to calibrate
voltage at 30% of Ur
0.00
UAmpComp100
Amplitude factor to calibrate
voltage at 100% of Ur
0.00
IAngComp5
Angle calibration for current at 5%
of Ir
0.00
IAngComp30
Angle pre-calibration for current
at 30% of Ir
0.00
IAngComp100
Angle pre-calibration for current
at 100% of Ir
0.00
Section 12 1MRK 505 291-UEN A
Monitoring
268
Application manual