L1
IL1
IL2
IL3
L2 L3
Protected Object
CT 600/5
Star Connected
IL1
IL2
IL3
IED
IEC13000002-4-en.vsdx
1
2
3
4
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
5
IN
IEC13000002 V4 EN
Figure 26: Star connected three-phase CT set with star point towards the protected object
Where:
1) The drawing shows how to connect three individual phase currents from a star connected
three-phase CT set to the three CT inputs of the IED.
2) The current inputs are located in the TRM. It shall be noted that for all these current inputs the
following setting values shall be entered for the example shown in figure 26.
CTprim=600A
CTsec=5A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.
In other words, currents are already measured towards the protected object.
Table continues on next page
1MRK 505 291-UEN A Section 4
Analog inputs
67
Application manual