EasyManua.ls Logo

ABB RET670 - Inverse Time Characteristics for Undervoltage Protection

ABB RET670
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 121. Inverse time characteristics for undervoltage protection
Function Range or value Accuracy
Type A curve:
=
< -
<
æ ö
ç ÷
è ø
k
t
U U
U
EQUATION1431-SMALL V1 EN
U< = U
set
U = U
measured
k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms
whichever is greater
Type B curve:
2.0
480
0.055
32 0.5
×
= +
< -
× -
<
æ ö
ç ÷
è ø
k
t
U U
U
EQUATION1432-SMALL V1 EN
U< = U
set
U = U
measured
k = (0.05-1.10) in steps of 0.01
Programmable curve:
×
= +
< -
× -
<
é ù
ê ú
ê ú
ê ú
æ ö
ê ú
ç ÷
ëè ø û
P
k A
t D
U U
B C
U
EQUATION1433-SMALL V1 EN
U< = U
set
U = U
measured
k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of 0.001
B = (0.50-100.00) in steps of 0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in steps of 0.001
P = (0.000-3.000) in steps of 0.001
Transformer protection RET670 2.0
1MRK 504 141-BEN C
Product version: 2.0
102 ABB

Table of Contents

Other manuals for ABB RET670

Related product manuals