EasyManua.ls Logo

ABB RET670 - Synchronizing, Synchrocheck and Energizing Check SESRSYN

ABB RET670
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control
Table 71. Synchronizing, synchrocheck and energizing check SESRSYN
Function Range or value Accuracy
Phase shift, j
line
- j
bus
(-180 to 180) degrees -
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ± 2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ± 2.0 degrees
Voltage difference limit between bus and line for synchronizing and
synchrocheck
(0.02-0.5) p.u ± 0.5% of U
r
Time delay output for synchrocheck when angle difference between bus
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
(0.000-60.000) s ± 0.2% or ± 35 ms whichever is
greater
Frequency difference minimum limit for synchronizing (0.003-0.250) Hz ± 2.5 mHz
Frequency difference maximum limit for synchronizing (0.050-0.500) Hz ± 2.5 mHz
Maximum allowed frequency rate of change (0.000-0.500) Hz/s ± 10.0 mHz/s
Breaker closing pulse duration (0.050-60.000) s ± 0.2% or ± 15 ms whichever is
greater
tMaxSynch, which resets synchronizing function if no close has been made
before set time
(0.000-6000.00) s ± 0.2% or ± 35 ms whichever is
greater
Minimum time to accept synchronizing conditions (0.000-60.000) s ± 0.2% or ± 35 ms whichever is
greater
Voltage high limit for energizing check (50.0-120.0)% of UBase ± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of UBase ± 0.5% of U
r
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (50.0-180.0)% of UBase ± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Time delay for energizing check when voltage jumps from 0 to 90% of
Urated
(0.000-60.000) s ± 0.2% or ± 100 ms whichever is
greater
Operate time for synchrocheck function when angle difference between bus
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
Min = 15 ms
Max = 30 ms
Operate time for energizing function when voltage jumps from 0 to 90% of
Urated
Min = 70 ms
Max = 90 ms
Transformer protection RET670 2.0
1MRK 504 141-BEN C
Product version: 2.0
82 ABB

Table of Contents

Other manuals for ABB RET670

Related product manuals