Chapter 6 - Operation 
104 3BHS335648 E82 UNITROL 1020 User Manual
CLOCK SET
0.0 V UN
AUTO NoLoad
0.0 kV UM
100.0% E
REM
SETPNT
12:45
MENU
I_MAIN MENU 1
REM
EXIT
12:46
ENTER
PARAM/SIG
CLOCK SET
TIME & DATE 02
REM
EXIT
12:47
SEL
SET DATE
SET TIME
MENU
ENTER
SEL, Oks
CLOCK SET
SET TIME
SET DATE
Change time and date settings with the panel
- Time format is always 24 hours
- Date format is always dd.mm.yy
Can be adjusted in remote and local operation
6.3.7 Setpoint Step
Apply a step to any setpoint. panel is in local mode.
It is the user’s responsibility to choose the right step type according to the actual generator mode. If
the wrong step is chosen, the value will also keep its value for 10 sec, but there is no influence on
the operation of the AVR.
PARAM/SIG
01 Commands
0103
0104
0105
0106
0107
AUTO Step
PF Step
VAR Step
MANUAL Step
OpenLoop Step
6.3.8 Save to EEPROM
PARAM/SIG
01 Commands
0101
0102
RESET ALARM
Save to EEPROM
Setting new parameters over the panel or over CMT changes the parameters in the volatile memory
only. To make the modification permanent, the entire parameter set must be saved.