Chapter 3 - Device Overview 
70 3BHS335648 E82 UNITROL 1020 User Manual
The number of samples is limited to 2000 samples/signal. If the SW-Option is disabled
the recording will be limited to 200 samples/signal.
3.4.4.7 Event Monitor
Events are stored on non-volatile flash and can be read out by MODBUS requests. Event
triggering signals are grouped as follows:
Generator state changes
Active Mode changes
Limiters ON and OFF
Alarms
Trips
Excitation ON (operation mode)
Parameter change
3.4.5 Miscellaneous Functions
3.4.5.1 History Logger
The History Logger records the last two hours of operation. A measurement sample of 12 defined
signals is stored in the non-volatile flash every minute. Each time the excitation is started the
default values are stored in the log to identify restart conditions.
Table 3-4 Recorded signal of History logger
Signal
Signal identification
Value of start Exc.
Machine voltage
Umrel
0%
Machine current
IM2rel
0%
Reactive power
Qrel
0%
AVR output PWM
PWM
50%
Generator state
GenState
0
AVR Control mode
Generator control mode
0
Machine frequency
fMachine
0Hz
Limiter status
Combined Limit
0
Active Power
Prel
0%
AVR input voltage (rectified)
Upwr
0V
Temperature of controller
Temperature DSP
0°C
3.4.5.2 FCB Control
Field circuit breaker control
FCB Control is an alternative way to control the field circuit breaker. The control is active,
when the FCB command signals are configured.