Chapter 3 - Device Overview
UNITROL 1020 User Manual 3BHS335648 E82 29
3.3.7 Analog Inputs
External setpoint input to Auto regulator
PF Remote Setpoint (Requires
PF/VAR SW)
External setpoint input to PF regulator
Var Remote Setpoint (Requires
PF/VAR SW)
External setpoint input to Var regulator
External setpoint input to Manual regulator
External setpoint input to open loop
UM Aux (Requires UM AUX SW)
Auxiliary supply to the summing point of Auto regulator
Auxiliary supply to the summing point of the PF/VAR regulator
Cooling Media Temperature
Input temperature measurement for the temperature influence limiter
Reserved for real-time simulator
PSS Power Injection
(Requires PSS SW)
PSS power injection point, scaling see PSS test interface
PSS Frequency Injection
(Requires PSS SW)
PSS frequency injection point, scaling see PSS test interface
PSS LeadLag Injection
(Requires PSS SW)
PSS lead lag injection point, scaling see PSS test interface
Input for external PSS signal
Digital Input 13(+) & 14(-)
Digital Input 15(+) & 16(-)
Digital Input 17(+) & 18(-)
Note: When configuring an external setpoint from the analog input list shown above, the
"Remote SP Enable" digital input should also be configured. For more information see
Chapter 3.3.5 Digital Inputs.
3.3.7.1 Level of the Analog Inputs
A minimum and maximum voltage level can be set for every analog input. This level
represents a defined scaling, which is shown in the table below.
PF Remote Setpoint
(Requires PF/VAR SW)
Var Remote Setpoint
(Requires PF/VAR SW)
Cooling Media Temperature
PSS Power Injection
(Requires PSS SW)
PSS Frequency Injection
(Requires PSS SW)
Scaling from 0.1% to 1.0%
PSS LeadLag Injection
(Requires PSS SW)
Scaling from 0.1% to 1.0%
Range symmetrically
adjustable