Chapter 3 - Device Overview
28 3BHS335648 E82 UNITROL 1020 User Manual
(
Requires Synchronization
SW)
- Angle is in a value where it would take the Total CB Closing Time for
the breaker to close at zero degrees with current speed and
acceleration.
- Sync Check demand active
- The command is active as long as the command Sync Check is active
Sync Check (Requires
Synchronization SW)
Sync Check demand to be active:
- Generator circuit breaker is open
- Machine voltage is higher than 50%
- Synchronization is possible (unit with Sync-Option)
- Synchronize is enabled
- Slip is between minimum slip and maximum slip
- Machine voltage is deviating from network voltage maximum Delta U
- Angle is between -maximum delta angle and +maximum delta angle
Control signal to governor to increase speed, pulses (Requires
Synchronization SW).
Control signal to governor to decrease speed, pulses (Requires
Synchronization SW).
Control signal to 2
nd
channel to take over control (Requires Double Channel
SW).
Trip indication, depending on the activated monitor functions (Requires
Double Channel SW)
Alarm indication, depending on the activated monitor functions (Requires
Double Channel SW)
Alarm indication, depending on the activated monitor functions (Requires
Double Channel SW)
Alarm indication, depending on the activated monitor functions (Requires
Double Channel SW)
Alarm indication, depending on the activated monitor functions (Requires
Double Channel SW)
Event of open diode (Requires Rotating Diode Monitoring SW)
Event of a shorted diode (Requires Rotating Diode Monitoring SW)
Indication that PSS is contributing (Requires PSS SW)
Fault ride through indication
(Sudden voltage dip at network)
Indication that Excitation is ON
Indication that Softstart is still active (ramping up of the SP)
Indication that Manual mode is active
Indication that PF/VAR mode is active
3.3.6.1 Polarity
Polarity can be configured for all digital input/output ports separately, and each one has a
separate polarity configuration when configured as input or output. Each DIO port can be
configured as only input or only output at the same time.
3.3.6.2 Forcing Digital Output Signals
Each digital output can be forced for test purposes by inverting its polarity. This will even
work when no output signal is selected.