Chapter 9 - Technical Data
174 3BHS335648 E82 UNITROL 1020 User Manual
9.1.3 Environmental data of AVR UNITROL 1020:
Permission ambient Temperature
Storage temperature maximum
Recommended storage temperature
cUL-Certification (CSA compliant)
Maximum heat sink temperature
UL 508, user group (ongoing)
Shock and bump, IEC 60255-21-2
Protection class of housing
(Generic immunity standard)
(Generic emission standard)
9.1.4 UL Certification
To use UNITROL 1020 in a UL compliant way, the following must be considered:
Max. surrounding air temperature 70 °C
UNITROL 1010 max output capability at 70 °C 5 A /150 V
UNITROL 1020 max output capability at 70 °C 10 A /150 V
Only 60/75 °C wires shall be used
Marking for proper connections for the power supply, control, load
For use in Pollution Degree 2 Environment
Grounding conductor terminal shall be green-colored or plainly identified with “G”, “GRD”,
“GND”, “GRND”, “Ground”, “Grounding” or IEC Publication 417, Symbol 5019.
9.1.5 Reliability UNITROL 1020
MTBF (MIL-HDBK-217F) GB(40°) 22.8 years
Failure rate in time GB(40°) 5000 FIT
Operational life time of capacitors > 100’000 h
Average ambient temperature 40 °C
Input power 3 phases
Exciter current (without external cap) 15 A