Chapter 3 - Device Overview
UNITROL 1020 User Manual 3BHS335648 E82 31
3.3.8 Analog Outputs
Pulse width modulation, control value is scaled from 0 to 100%. It
represents the actual field voltage output of 0.5 to 99%
Excitation voltage (absolute)
Received excitation input power voltage
Machine active power (relative)
Machine PF absolute, negative: -Q / positive for +Q
Analog continuous signal presenting difference between U
NET
and U
M
Fbias = f
NET
– f
NOM
– (Slip
MAX
– Slip
MIN
)/2- Slip
MIN
Output signal Fbias is forced to zero:
- Not in Sync mode
- Synchronization function not enabled (unit without Sync-Option)
- Network frequency is not between 45 to 66 Hz
Slip between Network and Machine frequencies
PSS test point 1, select signal over PSS test interface in CMT1000
PSS test point 2, select signal over PSS test interface in CMT1000
Note: The assignment of the analog outputs to the 2 terminals AO1 and AO2 can be
selected freely.
3.3.8.1 Level of the Analog Outputs
A minimum and maximum voltage level can be set for every analog output. This level
represents a defined scaling, which is shown in the table below.
Scaling according to min/max
PF setpoint
Scaling depending on PSS test
interface settings
Scaling depending on PSS test
interface settings