Chapter 5 - Commissioning
86 3BHS335648 E82 UNITROL 1020 User Manual
5.3 Setting Aids
All parameters have to be controlled at the first commissioning.
See the description of the parameters in Chapter 3.4.1.6 Description of
Parameters and settings recorded in Chapter 7.3 - Standard Procedures
for Maintenance.
Parameter Settings, Default Values
Overview of parameter blocks
Voltage Droop Compensation
5.3.1 Setting Aids
5.3.1.1 Setup \ System Data, Ceiling Factor Kceil
The following section describes how to determine the Ceiling Factor in two different ways.
We recommend the measuring method. Measuring method:
=
Uemax: Maximum output voltage
Ueo: Output voltage at nominal
voltage of the machine
(machine in no-load
operation)
Regulator
E
SM
U
PWR
U
emax
U
eo
UM Nominal