Chapter 6 - Operation 
136 3BHS335648 E82 UNITROL 1020 User Manual
Adjust Limiters Temperature
Influence
Setup \ Limiters \ Temp
Influence
IM and Ie nominal values can
be changed in System Data
window.
Adjust Setpoint Range new window
Initial SP refers to the Initial setpoint of the operation mode.
Setup \ Setpoints \ Auto
The Initial Setpoint (SP) of Auto
mode is the final value of the Soft
Start ramp. For more information
refer to Chapter 3.4.2.1 Soft Start.
1. Parameter configuration: "SYNC
DisableCBCheck".
For more information see Chapter
3.4.2.7 Synchronization (SYNC)
2. Parameter configuration: "Enable
PF/VAR initial setpoint” will set SP
to initial value in case PF/VAR is
preselected when changing to grid
parallel operation.
3. Parameter configuration: "Loose
grid go to initial SP” will set SP to
initial value when going to island
operation.
4. Parameter configuration: "Reset
SP to initial SP will set SP to initial
value in case “Reset Setpoint” is
activated.
False (default)
True
1