 Chapter 6 - Operation
UNITROL 1020 User Manual 3BHS335648 E82 141
2. Open input DI10 by
clicking on the white
box.
3. Select input: "Parallel
with Grid Status"
4. Result: DI10 configured
4
The procedure above only changes the parameters in the volatile memory.
To make the modification permanent (even after restarting the AVR), all the parameters
have to be stored in the non-volatile EEPROM.
Save parameters during CONTROL Access:
- Unit: Menu bar CMT1000 \ File \ Write Parameters to EEPROM
- Hard disk: Menu bar CMT1000 \ File \ Save Parameter File