Chapter 5 - Commissioning
90 3BHS335648 E82 UNITROL 1020 User Manual
5.3.1.14 Setup \ Diode Monitoring
The Nominal Exciter Frequency has to be adjusted. For the others, the default value has to
be kept.
f
exc
= P
exc
x f
gen
/ P
gen
Nominal Exciter frequency
Number of pole pairs in exciter machine
Nominal Generator frequency
Number of pole pairs in generator
5.3.1.15 Setup \ PSS
ABB offers PSS parameter calculation and stability studies, contact us for further
questions.
For more information refer to following documents:
UNITROL 1020 Power System Stabilizer (PSS) Engineering Notes
Doc. No. 3BHS351450 E01
Simplified Computer Representation for Power System Stability Studies
UNITROL 1020 and UNITROL 1010
Doc. No. 3BHS354059 E01
See manufacturer’s details, Chapter 1.5 - Manufacturer’s Address.
5.3.1.16 Setup \ Double Channel
The configuration of Double Channel depends on the application and connections. For
detailed information about configuration, refer to 3.4.4.4 Double Channel (DCH).
5.3.1.17 Tune \ Setpoint Adjust, Step
Maximum adjustable setpoint jump during 10 s
5.3.1.18 Tune, Order of Priorities
If several operating modes are selected simultaneously by the digital inputs, the following
order of priority applies:
Only active, if Gen CB Closed status is active and