EasyManuals Logo

AccuEnergy Acuvim II series User Manual

AccuEnergy Acuvim II series
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
138
2. Display of Analog Output
Value of analog output is displayed in hex on screen. The relationship between
displayed value and real value of analog output is:
Real value = ×20mA (current output mode)
or Real value = ×5V (voltage output mode)
As shown in Fig 5-21, the displayed value of AO1 is 0x0800, so the real value of
AO1 is (0x0800/4096) ×5V or (0x800/4096) ×20mA.
Fig 5-21 AO value read on screen
3. Parameter Setting
Take AXM-IO21 (AXM-IO2 module in logic NO.1) for example.
“Electrical quantities relative to AO1 (10C2H)” register: this register determines
which electrical quantity AO1 should be relative to. (see Chapter 6 for
explaination). For example, if this register is “0”, then AO1 is relative to
Displayed Value
4096
Displayed Value
4096

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy Acuvim II series and is the answer not in the manual?

AccuEnergy Acuvim II series Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuvim II series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals