Reactive power Qa, Qb and Qc: -4800~4800 Var, real setting value is- 4800~4800.
System reactive power: -14400~14400 Var.
Apparent power Sa, Sb and Sc: 0~4800VA, real setting value is 0~4800.
System apparent power: 0~14400VA, real setting value is 0~14400.
Power factor PFa, PFb, PFc and System power factor: -1~1, real setting value is
-1000~1000.
3) AO output range setting:
AO output value range setting start point (Y1), AO1 output value range setting
point 2 (Y2), AO1 output value range setting point 3 (Y3) and AO output value
range setting end point (Y4) are increasing value, while they should be within
range of AO output value.
When AO type is 0~20mA, the corresponding range is 0~24mA, the setting
value range is 0~ 4915, and the relationship is mA=setting value*20/4096.
When AO type is 4~20mA, the corresponding range is 4~24mA, the setting
value range is 819~ 4915, and the relationship is mA=setting value*20/4096.
When AO type is 0~5V, the corresponding range is 0~6V, the setting value
range is 0~ 4915, and the relationship is V=setting value*5/4096.
When AO type is 1~5V, the corresponding range is 1~6V, the setting value
range is 819~ 4915, and the relationship is V=setting value*5/4096.
Please note:
a> If the voltage input wiring of the meter is 2LL or 3LL, then the analog outpus
relative to phase voltage, neutral current, phase active/reactive/apparent
power and phase power factor will always be 0.
b> The maximum of analog output is 1.2 times the range.