136
When number is 2, which includes (X1, Y1), (X2, Y2) and (X4, Y4), only AO
following value range setting start point, AO1 following value range setting
point 2, AO following value range setting end point, AO1 output range setting
start point , AO1 output range setting point 2 and AO1 output range setting
end point should be set.
When number is 3, which includes (X1, Y1), (X2, Y2) , (X3, Y3) and (X4, Y4), only
AO following value range setting start point, AO1 following value range setting
point 2, AO1 following value range setting point 3 and AO following value
range setting end point should be set. At the same time, AO1 output range
setting start point, AO1 output range setting point 2, AO1 output range setting
point 3 and AO1 output range setting end point should be set.
2) Following value range setting:
AO following value range setting start point (X1), AO1 following value range
setting point 2 (X2), AO1 following value range setting point 3 (X3) and AO
following value range setting end point (X4) are increasing value, while they
should be within range of AO following value. Otherwise, the function of AO
will be aected.
Frequency: 45HZ~65HZ, real setting value is 4500~6500(50Hz or 60Hz type);
300.00Hz ~ 500.00Hz, real setting value is 30000 ~ 50000(400Hz type).
Phase voltage V1, V2, V3 and average phase voltage: 0~480V, real setting value
is 0~4800.
Line voltage V12, V23, V31 and average line voltage: 0~831V, real setting value is
0~8310.
Current I1, I2, I3 and average current: 0~10A, real setting value is 0~10000.
Power Pa, Pb and Pc: -4800~4800W, real setting value is -4800~4800
System power: -14400~14400W, real setting value is -14400~14400.