223
e). Set MAX INFO FRAM in the third setting page, such as 1. The BACnet MS/ TP
MAX INFO FRAM default value is 1, and the user defined range of MAX INFO
FRAM is 1~255. Users may set the parameters pointed out in Fig 5-91. After
setting the BACnet MS/TP MAX INFO FRAM, press the "V/A" key to accept. Press
the "P" key to go to the fourth setting page for the module reset.
Fig 5-84
f ). Set resetting mode in the fourth setting page. Select “RESET to reset the
module. Selecting “NO” will not reset the module. Selecting "RESET" will load the
module with modify settings. Press the "V/A" key to go to the setting page and
the parameter pointed out in Fig 5-92 will ash. Press the "P" or "E" key to select
the conguration mode. Press the "V/A" key to accept.
Note: When conguring BACnet module settings completely, users must select
“RESET to restart module and new settings will take eect.