246
Address Parameter
Format
code
Range
Data
type
Property
1030H Parity Setting2
0: EVEN 1: odd 2:NON2
3:NON1
word R/W
1031H
Communication
address2
1~247 word R
1032H
Alarming group
number
F1
0: no alarming record
1~16: last alarming record
group number
word R
1033H SOE group number F1
0: no SOE record
1~20: last SOE group
number
word R
1034H Run time (high)
F2 0~999999999
word R
1035H Run time (low) word R
1036H
Expanded
IO Modules
connecting status
Bit0: AXM-IO11;
Bit1: AXM-IO12;
Bit2: AXM-IO21;
Bit3: AXM-IO22;
Bit4: AXM-IO31;
Bit5: AXM-IO32;
0: disconnected
1: connected
word R
1037H Reserved
1038H
2
nd
communication
selection
2: Mesh 1: BACnet Protocol
0: Other Protocol
word R/W
1039H
Ten years download
setting enable
1: enable is valid word R/W
103AH
Fee of sharp
demand clear
0x0A: clear
Other: not clear
word R/W
103BH
Fee of peak demand
clear
0x0A: clear
Other: not clear
word R/W
103CH
Fee of valley
demand clear
0x0A: clear
Other: not clear
word R/W
103DH
Fee of normal
demand clear
0x0A: clear
Other: not clear
word R/W
103EH Total fee of demand clear 0x0A: clear Other: not clear word R/W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy Acuvim II series and is the answer not in the manual?

AccuEnergy Acuvim II series Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuvim II series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals