246
Address Parameter
Format
code
Range
Data
type
Property
1030H Parity Setting2
0: EVEN 1: odd 2:NON2
3:NON1
word R/W
1031H
Communication
address2
1~247 word R
1032H
Alarming group
number
F1
0: no alarming record
1~16: last alarming record
group number
word R
1033H SOE group number F1
0: no SOE record
1~20: last SOE group
number
word R
1034H Run time (high)
F2 0~999999999
word R
1035H Run time (low) word R
1036H
Expanded
IO Modules
connecting status
Bit0: AXM-IO11;
Bit1: AXM-IO12;
Bit2: AXM-IO21;
Bit3: AXM-IO22;
Bit4: AXM-IO31;
Bit5: AXM-IO32;
0: disconnected
1: connected
word R
1037H Reserved
1038H
2
nd
communication
selection
2: Mesh 1: BACnet Protocol
0: Other Protocol
word R/W
1039H
Ten years download
setting enable
1: enable is valid word R/W
103AH
Fee of sharp
demand clear
0x0A: clear
Other: not clear
word R/W
103BH
Fee of peak demand
clear
0x0A: clear
Other: not clear
word R/W
103CH
Fee of valley
demand clear
0x0A: clear
Other: not clear
word R/W
103DH
Fee of normal
demand clear
0x0A: clear
Other: not clear
word R/W
103EH Total fee of demand clear 0x0A: clear Other: not clear word R/W