257
Current I1, I2, I3 and average current: 0~10A, real setting value is 0~10000
.
Power Pa, Pb and Pc: -4800~4800W, real setting value is -4800~4800
System power: -14400~14400W, real setting value is -14400~14400.
Reactive power Qa, Qb and Qc: -4800~4800 Var, real setting value is-4800~4800.
System reactive power: -14400~14400 Var.
Apparent power Sa, Sb and Sc: 0~4800VA, real setting value is 0~4800.
System apparent power: 0~14400VA, real setting value is 0~14400.
Power factor PFa, PFb, PFc and System power factor: -1~1, real setting value is
-1000~1000.
3) AO output range setting:
AO output value range setting start point, AO1 output value range setting point
2, AO1 output value range setting point 3 and AO output value range setting
end point are increasing value, while they should be within range of AO output
value.
When AO type is 0~20mA, the setting value range is 0~ 4915, and the
relationship is mA=setting value*20/4096.
When AO type is 4~20mA, the setting value range is 819~ 4915, and the
relationship is mA=setting value*20/4096.
When AO type is 0~5V, the setting value range is 0~ 4915, and the relationship
is V=setting value*5/4096.
When AO type is 1~5V, the setting value range is 819~ 4915, and the
relationship is V=setting value*5/4096.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy Acuvim II series and is the answer not in the manual?

AccuEnergy Acuvim II series Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuvim II series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals