267
Address Parameter Code Range Data type Property
41A0H~41A5H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41A6H
MAX of apparent power
demand
F15 -32768~32767 int R
41A7H~41ACH
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41ADH
MAX of voltage
unbalance factor
F17 -32768~32767 int R
41AEH~41B3H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41B4H
MAX of current
unbalance factor
F17 -32768~32767 int R
41B5H~41BAH
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41BBH MAX of V1(V12) THD F18 -32768~32767 int R
41BCH~41C1H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41C2H MAX of V2(V31) THD F18 -32768~32767 int R
41C3H~41C8H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41C9H MAX of V3(V23) THD F18 -32768~32767 int R
41CAH~41CFH
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41D0H MAX of I1 THD F18 -32768~32767 int R
41D1H~41D6H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41D7H MAX of I2 THD F18 -32768~32767 int R
41D8H~41DDH
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
41DEH MAX of I3 THD F18 -32768~32767 int R
41DFH~41E4H
Time stamp: yyyy:mm:
dd:hh:mm:ss
F3 time int R
The addresses for the MIN value of the above parameters are located in 41E5H to 4293H. They
have the same format as the MAX value.