24 I-210+ User Manual
Errors and Cautions
Troubleshooting
Symptom Probable Cause Remedy
High/low
Momentary kW
display
Socket wiring error. Rewire according to applicable diagram.
Meter internal wiring defective.
Check the voltage and current
connectors are seated properly. Check
the leads for damage.
Defective sensor. Replace meter.
Meter overheats
Meter socket has insufficient capacity
or is not adequately wired.
Replace meter socket with a heavy-duty
model.
Meter is overloaded.
Change to transformer rated installation
with correctly sized CTs.
Poor connection at socket terminal. Replace socket terminal.
Meter runs slow
Socket wiring error. Rewire according to applicable diagram.
Meter internal wiring defective.
Check that voltage and current
connectors are seated properly. Check
the leads for damage.
Defective sensor. Replace meter.
No
display
Circuit de-energized. Check circuit voltages
Test link(s) open Close test links.
Meter internal wiring defective
Check the voltage leads are properly
connected. Also check the wires for
damage
message
on display
Meter detected an internal condition
that may affect the meter data.
Replace the meter and return to factory
for service.