Zone Attributes
Zone attribute descriptions
Double knock: The panel will require 2
activations of the same detector before causing
an alarm condition. This setting is used as a false
alarm measure.
Note: Double knock must not be used on
zones having magnetic door/window
contacts.
Omit Prevent: The panel will prevent the zone
from being omitted by the user when setting the
system.
Zone Delay: The panel programs a zone delay
to 800mS to give extra immunity to false alarms.
20 4PI175 issue 1_6/01
Engineering information Accenta/Optima G3 Intruder system
Zone Attributes
Zone
Attributes
Double Knock
Omit Prevent
Zone Delay
2
3
1
6
Attack
Zone n
selected
Zone n
deselected
5
6
7
2
3
4
1
8
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Press number button to
select / deselect
zone delay, Omit zone or Double knock
0
Deselect all zones
ZONE1-8
Momentarily On
Appropriate
Zone indicator
is lit to show
zone having
800mS delay,
Omit prevent
or double knock.
Factory defaults:
All zones have
delay of 300mS
No Zones are
set as omit prevent
No zones are
in double knock
Day
Enter Engineer program mode
Exit to zone type
Exit zone attributes
Leave program mode
Tamper
Attack
Acknowledge
Day
Day
Reset
Reset
Reset
Example: To configure zones 4 and 5 for ‘Double knock’ operation, Press:
6
Prog
9 9 9 9
5
Reset Reset Reset
1 4