3000EN Series: Installation Instructions
4-14
Configurable Zone Type Options
Auto Restore
Faults on zones set for this option are cleared and restore messages sent upon
restoral of faults.
Vent Zone
Zones set for this option are ignored if faulted when arming the system, but
will be protected if the zone is later restored (e.g., an open window can be
ignored when arming, but if the window is later closed, it will be protected;
opening the window again causes an alarm.)
Bypass when Disarmed
Zones set for this option can be bypassed only while the system is disarmed.
Bypass when Armed
Zones set for this option can be bypassed while system is armed.
Dial Delay
Alarms on zones set for this option participate in dial delay central station
reporting, if system dial delay enabled in field *50.
Fault Delay
Faults on zones set for this option are delayed by the time set in field *53. Do
not use this option if using entry/exit delay for this zone type.
Faults Display
Selects how faults on zones set for this zone type are displayed.
Power Reset/Verification
Selects whether the system resets power (when user enters code + OFF), and
whether the system performs alarm verification (see description for zone type
16 in Section 3 Programming Overview) when a fault occurs on these zones.
Use Entry Delay 1/2
Selects whether to use the system’s entry delay times.
Use Exit Delay
Selects whether to use the system’s exit delay time.
Interior Type
Zones set for this option are treated same as standard zone type 4 (bypasses
when armed STAY, faults displayed).
Alarm Sounds
Selects the type of alarms sound for zones set for this zone type.
Bell Timeout
Alarm sounds on zones set for this option remain for the duration set in fields
*32 and *33.
Fire Zone
Zones set for this option respond in the same manner as if programmed for
zone type 9. Do not set fire zones to respond as a “fault” in entries 1-6.
Trouble Sounds
Selects the type of trouble sounds for zones set for this zone type (periodic
beeps = once every 30 seconds; trouble beeps = rapid beeping).
Chime Enable
Zones set for this option cause a chime when Chime mode is on.

Table of Contents

Other manuals for ADT SASW3000EN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ADT SASW3000EN and is the answer not in the manual?

ADT SASW3000EN Specifications

General IconGeneral
BrandADT
ModelSASW3000EN
CategorySecurity System
LanguageEnglish

Related product manuals