GESTIONE COMPRESSORE (CP)
Il microprocessore attiva il compressore in base alla tempe-
ratura d’ingresso dell’acqua, controllando anche il numero
massimo di accensioni orarie.
GESTIONE DELLA POMPA DELL’ACQUA SULL’EVAPORATORE
La pompa dell’acqua sul lato evaporatore viene messa in
funzione per prima in fase di avviamento, dopo 60 secondi
parte il compressore.
Dopo l’avviamento questa pompa rimane sempre in funzione,
allo spegnimento dell’unità rimane in funzione per 1 minuto.
GESTIONE DELLA VALVOLA INVERSIONE CICLO (VIC)
La valvola d’inversione ciclo viene utilizzata nel cambio di
funzionamento Freddo/Caldo.
AUTOSTART CON “START MEMORY”
L’unità, al ritorno della tensione, si porrà nello stesso stato
precedente al black-out. Se la macchina era in funzione,
riprenderà il suo funzionamento, se, invece, era spenta,
rimarrà spenta.
COMPRESSOR MANAGEMENT (CP)
The microprocessor activates the compressor according to
the water inlet temperature, and controls the maximum
number of hourly start-ups.
WATER PUMP CONTROL ON EVAPORATOR
The water pump on the evaporator side is first activated
during start-up; after 60 seconds the compressor is activa-
ted.
The pump remains in operation after start-up and remains
on for 1 minute after unit power down.
CONTROL OF THE REVERSING VALVE (VIC)
The reversing valve is used to change Cooling/Heating ope-
ration of the unit.
AUTOSTART WITH “START MEMORY” FUNCTION
The unit will return to pre-power failure status when the
power supply is restored, i.e. it will resume operation if ope-
rating at the time of the power failure, or it will remain off if
that was its pre-power failure status.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC AN R407C and is the answer not in the manual?

AERMEC AN R407C Specifications

General IconGeneral
BrandAERMEC
ModelAN R407C
CategoryChiller
LanguageEnglish

Related product manuals