EN
1205. 6755517_02
23
16. SOUND DATA
S
Aermec determines sound power values in
agreement with the 9614 Standard, in com-
pliance with that requested by Eurovent cer-
tification.
Sound pressure measured in free field condi-
of unit, in compliance with ISO 3744 regula-
tions.
KEY
- Water input temperature 12 °C
- Temperature of produced water 7 °C
- External air temperature 35 °C
ANL
125 250 500 1000 2000 4000 8000
100 76.0 44.0 58.0 61.2 66.0 71.4 72.0 68.9 60.5 48.6
150 77.0 45.0 59.0 62.4 67.3 72.2 72.7 69.7 61.5 49.6
17. PARAMETER CALIBRATION OF
SAFETY AND CONTROL
CONTROL PARAMETERS
ANL
Cooling set point °C 4 7 18
Heating set point °C 35 45 50
Defrosting mode °C -9 3 4
Total differential °C 3 5 10
Autostart auto
CALIBRATION
THERMOMAGNETIC ANL60HZ
Models 60Hz
Compressors magnet
circuit breakers
Pumps magnet
circuit breakers
Fan magnet
circuit breakers
19,0 A 3,5 A Fixed 6A (also for auxiliary)
10,0 A 1,8 A Fixed 6A (also for auxiliary)
23,0 A 5,7 A Fixed 6A (also for auxiliary)
12,5 A 3,0 A Fixed 6A (also for auxiliary)
100H 150H
SAFETY AND CONTROL COMPONENTS ELECTRIC DATA
High pressure pressure switch
bar
42 42
Low pressure pressure switch
cold
bar
4 4
PdC bar
2 2
High pressure transducer
bar