EN
1205. 6755517_02
28
COMPONENTS SUPPLIED AS STANDARDS
1 Water filter
2 Differential pressure switch
3 Scambiatore a piastre
4
6 Safety valve
7 Expansion tank
8
9 Storage tank
12 Pump
NOT SUGGESTED COMPONENTS PROVIDED TO LOAD INSTALLER
5 anti vibration joints
7
10 Drain cock
11 Ball Stop
13 Manometer
ATTENTION
The choice and the installation of
components external to the
installer, who must operate accor-
ding to the rules of good technical
design and in compliance with the
regulations in force in the country
of destination.
ATTENTION
The hydraulic pipes connecting to
the machine must be properly si-
zed to the actual flow of water re-
quired by the system in operation.
The water flow to the exchanger
must always be constant.
ATTENTION
Carefully wash the plant, before
connecting the unit. This allows
cleaning to remove any residue
such as weld spatter, slag, rust or
other impurities from the pipes.
These substances may otherwise
accumulate in and cause a machi-
ne malfunction. The connecting
pipes should be supported so as
not to weigh, with their weight on
the unit
20.3.
3
PD
4
4
12
5
5
1
8
13
7
11
6
8
9
10
11
13
7
HYDRAULIC
COMPONENTS
ANL
HYDRAULIC COMPONENTS
SUGGESTED EXTERNAL UNIT