Power dedicated to domestic water production
Index - String
MIN
value
MAX
value
Parameter function
0% 100%
In those units that can produce domestic water, once this function has been activated
it is possible to decide the percentage of power to use for the production. This function
allows you to set a threshold to guarantee reduced energy consumption during domestic
water production.
Standby time in Input/Output
Index - String
MIN
value
MAX
value
Parameter function
0
secon-
ds
600
secon-
ds
This parameter allows you to establish the standby time (in seconds) for reversing the
3-way valve inserted in the system for producing domestic water.
Standby time in Input/Output
Index - String
MIN
value
MAX
value
Parameter function
03
This parameter enables the possibility to join the ID digital clamp (marked on the electric
card enclosed with the unit as TRA) with a room thermostat on which the functioning of
the compressors and supplementary electric heaters will be disabled.
Remember also that setting this parameter with a value of:
• 1 or 2, you ENABLE this function
• 0 or 3, you DISABLE this function
Remember that the OPEN status of the clamp means:
• the function blocks the compressors and electric heaters if the parameter is set at 1
• the function blocks the compressors, pump and electric heaters if the parameter is
set at 2
• the pump alarm (as in the previous software version), if the parameter is set at 3
Remember also that by setting this parameter at 3, the moducontrol card is compatible
with the previous software version (3.6).
Enabling flow switch bypass
Index - String
MIN
value
MAX
value
Parameter function
01
In those units that produce domestic water, the flow switch alarm can be bypassed to
allow the correct synchronisation between a diverting valve installed in the system, and
unit functioning during the production of hot domestic water.
Time for flow switch bypass
Index - String
MIN
value
MAX
value
Parameter function
0
secon-
ds
300
secon-
ds
This parameter allows you to establish the time (in seconds) for flow switch bypass.