READ LIST REGISTER:
ADDRESS DESCRIPTION
0 Type of machine: 0 – ANL,1 – ANLI, 2 – ANR/ANF/SRP, 3 – ANL-C
1 Type of inverter machine 0=longertek 1=APY
2 NTC1 input (TUA) (SIW)
3 NTC2 input (TIA) (SUW)
4 NTC3 input (TSB) (SS)
5 NTC4 input (TGP) (SGP)
6 NTC5 input (TAE) (SAE)
7 High pressure transducer input (AP) (TAP)
8 Low pressure transducer input (BP) (TBP)
9 0-10V dd input
10 Relay digital output status
11 Safety band on force OFF
12 Time until compressor start-up/switch-off
13 Hours of primary compressor operation (in thousands)
14 Hours of primary compressor operation
15 Number of peaks made by the compressor (in thousands)
16 Number of peaks made by the compressor
17 Major sw version
18 Minor sw version
19 Machine adjustment setpoint (including corrections)
20 Condensation control pressure setpoint
21 Pressure differential for condensation control
22 Hours of auxiliary compressor operation (in thousands)
23 Hours of auxiliary compressor operation
24 Number of peaks made by the auxiliary compressor (in thousands)
25 Number of peaks made by the auxiliary compressor
26 Power supplied by the machine (chiller ON-OFF) Use frequency (chiller inverter)
27 Compressor pressure drop during suction
28 Power requested from the inverter control
29 Dip-switch configuration (0x0000 = all OFF - 0x0FF = all ON)
30 ON_OFF command enablement status Season from panel or remote panel
31 Enablement status for room thermostat connected to ID3 input
32 Machine operation status: 0 - Chiller Off, 1 - Chiller On, 2 – Capacity control
injection, 3 – Defrosting for injection, 4 – Defrosting for reverse cycle
33 Electric heater/boiler accessory: 0=absent 1=electric heater 2=boiler
34 Inverter current APY
35 Inverter output voltage APY
36 Inverter BUS voltage APY
37 Inverter cooling fin temperature APY
38 Limit set point hot
COMANDI LETTURA DISPONIBILI
Read Holding Register

Other manuals for AERMEC MODUCONTROL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MODUCONTROL and is the answer not in the manual?

AERMEC MODUCONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMODUCONTROL
CategoryControl Unit
LanguageEnglish

Related product manuals